Specification Information for CC-Link Specification Information [CC-Link Version Description] | Version 1.0 | Original release of CC-Link | | Version 1.10 | This version allowed more convenient inter- station cable lengths of 20 cm or more. This specification change affects network devices and network cables. | | Version 2.0 | This version provides an 8-fold increase in the volume of data communication in the system and per station. Version 2.0 Compatibility |
CC-Link specification [Specification table of CC-Link Version 1.10 & 2.0]
The maximum number of occupied stations
| 4 stations | | Maximum Number of Devices per network | 64 Devices (See Note for Version 1.10 or 2.0) | | Communication speed | 10M / 5M / 2.5M / 625k / 156kbps | Communication system
| Broadcast Polling system | Synchronization system
| Frame synchronization system | Encoding system
| NRZI | Transmission path format
| Bus format (EIA RS485 conformance) | Transmission format
| HDLC conformance | Error control system
| CRC (X16+X12+X5+1) |
| Item | Maximum number of I/O
| Version 1.10
| Version 2.0 | Remote Input Points
| 2048
| 8192 | Remote Output Points
| 2048
| 8192 | Remote Input Words
| 256 | 2048 | Remote Output Words
| 256 | 2048 |
| Item | The number of link points per Device (Occupying 1 station)
| Version 1.10
| Version 2.0 (Extended cyclic setting) | ----
| 1 time setting
| 2 times setting
| 4 times setting
| 8 times setting | Remote Input Points
| 32
| 32 | 32 | 64 | 128 | Remote Output Points
| 32
| 32 | 32 | 64 | 128 | Remote Input Words
| 4 | 4 | 8 | 16 | 32 | Remote Output Words
| 4 | 4 | 8 | 16 | 32 |
| Item | The number of link points per Device (Occupying 2 stations)
| Version 1.10
| Version 2.0 (Extended cyclic setting) | ----
| 1 time setting
| 2 times setting
| 4 times setting
| 8 times setting | Remote Points In
| 64
| 64 | 96 | 192 | 384 | Remote Points Out
| 64
| 64 | 96 | 192 | 384 | Remote Words Out
| 8 | 8 | 16 | 32 | 64 | Remote Words In
| 8 | 8 | 16 | 32 | 64 |
| Item | The number of link points per Device (Occupying 3 stations)
| Version 1.10
| Version 2.0 (Extended cyclic setting) | ----
| 1 time setting
| 2 times setting
| 4 times setting
| 8 times setting | Remote Points In
| 96
| 96 | 160 | 320 | 640 | Remote Points Out
| 96
| 96 | 160 | 320 | 640 | Remote Words Out
| 12 | 12 | 24 | 48 | 96 | Remote Words In
| 12 | 12 | 24 | 48 | 96 |
| Item | The number of link points per Device (Occupying 4 stations)
| Version 1.10
| Version 2.0 (Extended cyclic setting) | ----
| 1 time setting
| 2 times setting
| 4 times setting
| 8 times setting | Remote Points In
| 128
| 128 | 224 | 448 | 896 | Remote Points Out
| 128
| 128 | 224 | 448 | 896 | Remote Words Out
| 16 | 16 | 32 | 64 | 128 | Remote Words In
| 16 | 16 | 32 | 64 | 128 |
Note for Maximum Number of Devices Version 1.10 Maximum Number of Network Slave products is 64 (in addition to the Master): The following equations also need to be satisfied:
(1*a) + (2*b) + (3*c) + (4*d) ? 64 a: Number of slave products that occupy 1 station b: Number of slave products that occupy 2 stations c: Number of slave products that occupy 3 stations d: Number of slave products that occupy 4 stations
(16*A) + (54*B) + (88*C) ? 2304 A: Number of Remote I/O products B: Number of Remote Device products C: Number of Local (Stand-by Master) and Intelligent Device products Note for Maximum Number of Devices Version 2.0 Maximum Number of Network Slave products is 64 (in addition to the Master): The following equations also need to be satisfied:
(a + a2 + a4 + a8) + (b + b2 + b4 + b8)*2 + (c + c2 + c4 + c8)*3 + (d + d2 + d4 + d8)*4 ? 64
(a*32 + a2*32 + a4*64 + a8*128) + (b*64 + b2*96 + b4*192 + b8*384) + (c*96 + c2*160 + c4*320 + c8*640) + (d*128 + d2*224 + d4*448 + d8*896) ? 819
(a*4 + a2*8 + a4*16 + a8*32) + (b*8 + b2*16 + b4*32 + b8*64) + (c*12 + c2*24 + c4*48 + c8*96) + (d*16 + d2*32 + d4*64 + d8*128) ? 2048
a: The number of units with 1 occupied station and 1 time setting b: The number of units with 2 occupied stations and 1 time setting c: The number of units with 3 occupied stations and 1 time setting d: The number of units with 4 occupied stations and 1 time setting a2: The number of units with 1 occupied station and 2 times setting b2: The number of units with 2 occupied stations and 2 times setting c2: The number of units with 3 occupied stations and 2 times setting d2: The number of units with 4 occupied stations and 2 times setting a4: The number of units with 1 occupied station and 4 times setting b4: The number of units with 2 occupied stations and 4 times setting c4: The number of units with 3 occupied stations and 4 times setting d4: The number of units with 4 occupied stations and 4 times setting a8: The number of units with 1 occupied station and 8 times setting b8: The number of units with 2 occupied stations and 8 times setting c8: The number of units with 3 occupied stations and 8 times setting d8: The number of units with 4 occupied stations and 8 times setting
(16*A) + (54*B) + (88*C) ? 2304 A: Number of Remote I/O products B: Number of Remote Device products C: Number of Local (Stand-by Master) and Intelligent Device products
CC-Link Version 1.10 cable (Using 110O terminators) If the entire system consists of Version 1.10 / 2.0 devices and Version 1.10 cables, then: - The shortest inter-station cable length is 20 cm under all conditions.
- Flexibility of cable length reduces work on wiring and setting devices.
- With no extra cable length required when devices are put adjacently,
you can use space effectively. - Different brand cables can be used within a single system.
If a system uses any module(s) compatible with Version 1.0 or cables compatible with Version 1.0, then follow the Version 1.0 specification for maximum overall cable extension length and inter-station cable length. 
Communication speed
| Inter-station cable length
| Maximum overall cable extension length | 156 kbps
| >= 20 cm
| 1200m | 625 kbps | >= 20 cm
| 900m | 2.5 Mbps | >= 20 cm
| 400m | 5 Mbps | >= 20 cm
| 160m | 10 Mbps
| >= 20 cm
| 100m |
Specification for T-Branch Transmission Instructions for Cable use
Version 1.10 cable is recommended for use with products of Version 1.10 or higher (Version 1.10, Version 2.0). If the entire system consists of the products of Version 1.10 or higher and uses Version 1.10 cable, then the required length of each inter-station cable is 20 cm or more. Different brand cables can be used within a single system. (See CC-Link specification for inter-station cable length and maximum overall cable extension length.) If a system uses either Version 1.0 devices and/or Version 1.0 cable, then follow the CC-Link Version 1.0 specification for inter-station cable length and maximum overall cable extension length. Different brand cables within a single system is not recommended. For a complete installation guide, including the different cable requirements, see the download page and read the CC-Link Installation Guide Network Compatibility of CC-Link Version 2.0
- A Version 1.10 Master station is compatible with both Version 2.0 slave stations and Version 1.10 slave stations. However, the Version 2.0 slave stations can only be used with their Version 1.10 capability (i.e. the Extended Cyclic Setting x1). They cannot provide any additional data volume.
- A Version 2.0 Master station is compatible with both Version 2.0 slave stations and Version 1.10 slave stations. However, the Version 1.10 slave stations can only be used within their capability. They cannot provide added data volume.


...return Specification for T-Branch Transmission The figures below show the network requirements when using T-Branch connections, and when not using the powered repeater units.   Repeater is not used When a repeater is not used and a T-Branch branch line is incorporated into the network configuration, the maximum network speed is 625kbps. When a repeater is not used, a branch line (T-Branch) can not branch off from another branch line.
Repeater is used Using a repeater enables the user to connect a branch at every communication speed. Using a repeater also allows the user to extend cable transmission distance. If a repeater is used and a branch line is incorporated into the network configuration using only a T-Branch connector (not a powered repeater), the maximum network speed is again only 625kbps. Only if all branch line connections incorporate a repeater, is the network capable of operating at all communication speeds. NOTE: When repeater is used, the specific repeater requirements are not specific to CC‑Link; it depends upon the type of repeater used. NOTE: Depending upon the repeater module, a Terminating Resistor may be necessary at the end of the branch connection, see the specific repeater module specifications for connection requirements.
Star Configuration A Star Configuration is considered a modification of a branch connection; with multiple connections at one point where the interval between branch connections is zero. A non-powered T-Branch hub at the multiple branch connection point may be used for network speeds less than 2.5Mbps. The use of a powered repeater hub at the multiple branch connection point is required for network speeds greater than 625kbps. Using a powered repeater also allows the user to extend cable transmission distance. NOTE: Depending upon the Repeater hub module, a Terminating Resistor may be necessary at the end of the branch connection, see the Repeater module specifications for Terminating Resistor connection requirements.
Communication Speed & Cable Length for T-Branch Connection | | Communication speed | 156kbps | 625kbps | 2.5M, 5M & 10M network speeds not allowed | | | Station-to-Station Cable Length | | Between master and local stations, intelligent device station, and adjacent stations | ≥ 1m | For a system configured only with remote I/O stations and remote device stations | | ≥ 2m | For a system configuration that contains local stations or intelligent device stations | | Between remote I/O stations and remote device stations | ≥ 30cm | | | Maximum No. of stations connected per branch line | 6 | See communication specification for the total number of connected stations | | Maximum trunk line length | 500m | 100m | The length of the cable between terminating resistors. The branch line length is not included. | | Total branch line length | 200m | 50m | Total length of all branch lines. | | Maximum individual branch line length | 8 m | Cable length per branch line | | Total transmission distance | 700 m | 150 m | (Trunk line length + all branch line lengths) |
....return
|